6 Communication settings and guide of HMI connecting with controller
4715H Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail.
In the setting mode
4716H Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail.
In the setting mode
4717H
Temperature unit display
selection
o
C : 1 (default),
o
F : 0. in the setting mode
4718H
Heating/Cooling control
Selection
Heating: 0 (default), Cooling: 1. in the setting mode
4719H Control Run/Stop setting
Run: 1 (default), Stop: 0. in the running mode
471AH
Communication write-in
selection
Communication write in disabled: 0 (default),
Communication write in enabled: 1.
In the setting mode
471BH Software Version V1.00 indicates 0 x 100
4729H AT Setting
OFF: 0 (default), ON: 1. in the adjusting mode
4733H CT monitor value
Unit is 0.1A. in the running mode
DTB9696VR:Address and Content of Word Register (corresponds to 4X in the HMI)
Address Content Explanation
1000H Process value (PV) Measuring unit is 0.1, updated one time in 0.4 second
1001H Set point (SV) Unit is 0.1,
o
C or
o
F
1002H Upper-limit of temperature range
The data content should not be higher than the
temperature range. In the setting mode
1003H Lower-limit of temperature range
The data content should not be lower than the
temperature range. In the setting mode
1004H Input temperature sensor type
Please refer to the contents of the “Temperature Sensor
Type and Temperature Range” for detail. In the setting
mode
1005H Control method
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram
control. In the setting mode
1006H Heating/Cooling control selection
0: Heating, 1: Cooling, 2: Heating/Cooling, 3:
Cooling/Heating. In the setting mode
- 74 -