6 Communication settings and guide of HMI connecting with controller
under the control of PID and the mode of )
1040H~
1047H
Actual step number setting inside
the correspond pattern
0 ~ 7 = N, indicate that this pattern is executed from step
0 to step N. in the setting mode
1050H~
1057H
Cycle number for repeating the
execution of the correspond pattern
0 ~ 99 indicate that this pattern has been executed for 1
~ 100 times. In the setting mode
1060H~
1067H
Link pattern number setting of the
correspond pattern
0 ~ 8, 8 indicates the program end. 0~7 indicates the
next execution pattern number after executing the
current pattern. In the setting mode
2000H~
203FH
Pattern 0~7 temperature set point
setting(Pattern 0 temperature is set
to2000H ~ 2007H)
-999 ~ 9,999. in the setting mode ~
2080H~
20BFH
Pattern 0~7 execution time
setting(Pattern 0 time is set to
2080H~2087H)
Time 0 ~ 900 (1 minute per scale). in the setting mode
~
DTB9696VR:Address and Content of Bit Register (corresponds to 1X in the HMI)
0810H Communication write-in selection Communication write in disabled: 0 (default),
Communication write in enabled: 1.
In the setting mode
0811H Temperature unit display selection
o
C/linear input (default): 1 ,
o
F : 0. in the setting
mode
0812H Decimal point position selection
Except for the thermocouple B, S, R type, all the
other thermocouple type are valid. (0 or 1).
In the running mode
0813H AT setting
OFF: 0 (default), ON : 1.
In the adjusting mode
0814H Control RUN/STOP setting
0: STOP, 1: RUN (default).
In the running mode
0815H STOP setting for PID program control
0: RUN (default), 1: STOP.
In the running mode
0816H Temporarily STOP for PID program control
0: RUN (default), 1: Temporarily STOP.
In the running mode
0817H Valve feedback setting status 0: w/o feedback (default), 1: feedback function.
0818H Auto-tuning valve feedback status 0: Stop AT (default), 1: Start AT
- 77 -